Leroy Somer Low Voltage Alternators

 Products: Leroy Somer LSA 52.3  1860kVA - 2500kVA 


Odoo image and text block

Overview

Manufactured by Leroy Somer

Brushless alternator with exciter
Single bearing or two bearing arrangement
Prime mover : diesel or gas engine

Compliance with :
IEC, VDE, NEMA, BS, CSA, UL1446, CE low voltage

Technical Features

Power Range (Elec) 50hz:

1860kVA - 2500kVA    (Prime Rated)

Power Range (Mech) 50hz:

1488kW - 2000kW    (Prime Rated)

Power Range (Elec) 50hz

2066kVA - 2778kVA    (Standby Rated)

Power Range (Mech) 50hz

1653kW - 2222kW    (Standby Rated)

Insulation Class:

Class "H"

Winding Pitch:

2/3 (wdg 6S)

No. of Wires:

6

Protection:

IP23 Enclosure

Altitude Rating:

≤ 1000 M

Overspeed:

2500 min - 1

Air flow:

1.8 m3/s, 50 Hz - 2.2 m3/s, 60 Hz

Excitation System Standard / AVR:

AREP+PMI D550

Excitation System Option / AVR:

AREP+PMI D550

Voltage regulation (Steady state):

± 0.5 %

Short-circuit current:

(3 IN / 10 s) 300% with AREP / PMG Option

Totale Harmonic distortion THD:

3.5% No Load <3.5% On Load

Waveform:

NEMA = TIF < 50

Mounting Configurations ( Standard)

SAE FLYWHEEL & BELLHOUSING
CLICK HERE TO CONFIRM MOUNTING
SAE 0 - 18

SAE 00 - 21

DOUBLE BEARING

Technical Feature Downloads

Brochure


Click to Download

Data Sheet


Click to Download

Drawings


Click to Download

Maintenance


Click to Download

AVR Data Sheet


Click to Download

Need more information or technical support?